Description
HIMA SB3073-EX – Intrinsically Safe Isolator (Thermocouple/RTD Input)
Product Overview
The HIMA SB3073-EX is an intrinsically safe isolator designed for hazardous industrial environments, specifically handling thermocouple, RTD, and millivolt input signals. It acts as a critical interface between field devices and control systems, providing triple isolation between power, input, and output to prevent dangerous energy transfer to explosive zones. This unit solves the problem of signal distortion and safety risks in harsh areas, converting field temperature signals into standard 4-20mA or 1-5V outputs for reliable transmission to DCS/PLC systems, while complying with strict explosion-proof standards.
Technical Specifications — SB3073-EX
| Parameter | Value |
|---|---|
| Product Model | SB3073-EX |
| Manufacturer | HIMA |
| Product Type | Intrinsically Safe Isolator (Thermocouple/RTD Input) |
| Power | 24VDC ±10% |
| Communication / Protocol | Supports bidirectional HART protocol |
| Operating Temperature | -20°C to 60°C |
| Mounting | DIN rail mounting |
| Dimensions (HxWxD) | 112.6mm × 99.0mm × 17.5mm |
| Weight | Approximately 150g |
| Typical Interfaces | Thermocouple/RTD input, 4-20mA/1-5V output |
| Compliance | GB3836.4-2000, (Ex ia) ⅡC explosion-proof grade, IEC 61511 |

HIMA SB3073-EX
Key Features and Benefits — SB3073-EX
- Intrinsically safe design: Suitable for Zone 0 hazardous areas, limiting fault energy to ensure on-site safety.
- Triple isolation: Separates power, input, and output ports to avoid signal interference and equipment damage.
- Versatile input compatibility: Accepts thermocouple (J/K/T/E etc.), RTD (Pt100/Cu50), and millivolt signals.
- Hot-swappable terminals: Facilitates on-site installation and maintenance without power shutdown.
- High conversion accuracy: Ensures stable and reliable signal transmission for precise process control.
Related Models
- SB3075-EX: HIMA 1-in-2-out intrinsically safe isolator, compatible with thermocouple/RTD inputs for dual-output scenarios.
- SB3042-EX: HIMA isolator with 4-20mA input/output, integrated power distribution and HART communication.
- F7553: HIMA SIL 3 safety controller, ideal for high-safety requirement systems in process industries.
- Z1004: HIMA safety module, compatible with HIMAX and HIMATRIX platforms for emergency shutdown support.
Installation and Maintenance — SB3073-EX
- Mount the unit on a standard DIN rail in a dry, dust-free control cabinet, avoiding direct exposure to moisture.
- Connect field sensors to input terminals and control systems to output ports, following HIMA’s wiring guidelines.
- Regular maintenance involves checking terminal connections for tightness and cleaning the unit surface to prevent dust buildup.
- Ensure the power supply voltage stays within the 24VDC ±10% range to maintain stable operation and isolation performance.