Description
- Model: CP471-00 S1
- Brand: Yokogawa Electric Corporation
- Series: CENTUM VP / CP471 Processor Series
- Core Function: Executes field-control logic and network processing
- Type: DCS processor module
- Key Specs: Dual-redundant Vnet/IP; battery-backed main memory; approx. 0.7 kg
- Compatibility: AFV30, AFV40, A2FV50 and A2FV70 field control units
- Condition: New Original (New Surplus) availability is supplier-dependent
Product Introduction
The YOKOGAWA CP471-00 S1 is a processor module for CENTUM VP field control units, serving as the computing core for control execution and Vnet/IP communication. Yokogawa specifies dual-redundant Vnet/IP support and allows two processors to operate in a redundant configuration on compatible duplexed field control units.
For a maintenance team, software compatibility is the first checkpoint. Current Yokogawa documentation states that CP471 operates with the Control Function for Field Control Station from the specified supported CENTUM VP releases, while replacement of CP461 requires authorized service work under Yokogawa’s documented procedure. The module weighs about 0.7 kg, and its main memory is battery-backed for up to 72 hours during power failure.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Model | CP471-00 S1 |
| Manufacturer | Yokogawa Electric Corporation |
| Product Type | Processor Module |
| System | CENTUM VP DCS |
| Supported Field Control Units | AFV30, AFV40, A2FV50, A2FV70 |
| Network Interface | Dual-redundant Vnet/IP |
| Redundancy | Dual-redundant processor configuration |
| Main Memory Protection | Battery backup |
| Memory Retention During Power Failure | Max. 72 hours |
| Battery Recharge Time | Min. 48 hours |
| Approx. Weight | 0.7 kg |
| Mounting | CENTUM VP Field Control Unit |
| Operating System / Software | Control Function for Field Control Station |
| Typical Application | Process control, field I/O processing, DCS communication |
| Installation Status | Legacy CENTUM VP hardware; verify current lifecycle |
Yokogawa’s official specification confirms the dual-redundant Vnet/IP interface, approximately 0.7 kg weight, battery-backed memory, and 72-hour maximum memory retention during power failure.

YOKOGAWA CP471-00 S1
Key Features and Practical Value
- Dual-redundant Vnet/IP for compatible CENTUM VP field-control architectures.
- Supports redundant processor operation on duplexed field control units.
- Battery-backed main memory helps preserve retained data during a power interruption.
- Designed specifically for Yokogawa CENTUM VP hardware rather than general-purpose PLC use.
- Supports online replacement in documented dual-redundant configurations.
- Suitable for installed-system maintenance where matching the original field-control architecture matters.
The important point is compatibility. A processor that physically fits the rack is not automatically a valid substitution.
Typical Applications
This processor is suited to process plants using CENTUM VP, including oil and gas, petrochemical, power, chemical, and other continuous-process installations.
In a typical field control station, the processor handles control execution and system communication while the associated I/O and bus modules interface with the process. CP471 can be used in dual-redundant configurations where the host field-control unit supports it.
Related Models
CP471-01 — Explosion-protection version of the CP471 processor family. The applicable suffix must match the field-control-unit configuration and installation requirements.
CP461 — Earlier CENTUM VP processor generation that CP471 can replace under specific Yokogawa conditions. Yokogawa states that direct CP461-to-CP471 replacement requires the appropriate software revision and authorized service procedure.
EC401 — ESB bus coupler used with CP471 systems; Yokogawa specifies a required style code of S3 or later for compatible CP471 installations.
AFV40 / A2FV50 / A2FV70 — Compatible CENTUM field-control-unit families documented for CP471 use.
Installation and Maintenance
Before replacement, record the processor revision, CENTUM VP software release, field-control-unit model, ESB coupler style, redundancy arrangement, and network configuration.
Do not mix processor generations casually. Yokogawa specifically states that CP471 and CP461 cannot coexist in one dual-redundant processor pair, although an existing CP461 pair may be replaced online by a CP471 pair under the prescribed conditions.
A practical maintenance step: photograph the installed module and all configuration identifiers before removal. Then verify the software environment against the Yokogawa compatibility requirements. After installation, check processor status, Vnet/IP communication, redundancy state, diagnostics, and field-control execution.
Quality Inspection and Test Procedure
For a New Surplus, used, or refurbished spare, inspection should be documented.
1. Inbound inspection
- Verify part-number traceability and serial number.
- Inspect the housing, connector and label condition.
- Check for corrosion, impact marks, or previous repair evidence.
- Verify supplied documentation and accessories where applicable.
2. Live Test
Use a compatible CENTUM VP field-control test environment.
- Confirm power-up and processor diagnostics.
- Verify Vnet/IP communication.
- Check redundant operation where the test setup supports it.
- Confirm stable operation under continuous test conditions.
- Generate a Test Report.
3. Electrical testing
Check applicable supply and grounding conditions according to the Yokogawa maintenance procedure. Insulation or withstand testing should only be performed where the manufacturer’s procedure explicitly permits it.
4. Firmware and configuration verification
Record the installed software or firmware revision where accessible. Preserve module identification and configuration records before shipment.
5. Final QC
Apply QC approval, antistatic packaging, protective cushioning, and a dated inspection label. Test photos or video can be supplied for customer review.
Technical Replacement Pitfalls
Software revision mismatch: This is the big one. CP471 operation depends on the supported Control Function for Field Control Station software version. Verify the actual CENTUM VP release before ordering.
ESB bus coupler mismatch: CP471 requires compatible EC401 hardware. Yokogawa specifies style code S3 or later for the documented configuration.
CP461 mixed configuration: Do not install CP471 beside CP461 in a dual-redundant pair. Yokogawa explicitly prohibits that arrangement.
Wrong field-control-unit model: Check whether the host is AFV30, AFV40, A2FV50, or A2FV70 before purchase. The processor is not a universal Yokogawa CPU.
Battery condition: The memory-retention figure assumes the battery system is within its specified condition. For an older spare, battery status deserves inspection rather than assumption.
Procurement Guidance
For an international MRO purchase, identify the item as Yokogawa CP471-00 S1 processor module, then specify condition, hardware style, country of origin, test status, warranty, lead time, and Incoterms on the quotation.
For customs documentation, use a precise functional description such as “industrial process-control DCS processor module” rather than a vague description such as “electronic board.” The exact HS classification should still be confirmed against the export and import jurisdictions involved.
Quick Conclusion
- CP471-00 S1 is a CENTUM VP processor module for Yokogawa field control units.
- It supports dual-redundant Vnet/IP and redundant processor configurations.
- Main memory is battery-backed for up to 72 hours during power failure under the published specification.
- Compatibility with the CENTUM VP software release and EC401 style code must be verified before replacement.
- CP471 is not a generic PLC CPU; it should be purchased as a configuration-matched CENTUM VP spare.