Description
Woodward 8444-1019 – UMT 1 Measuring Transducer
Product Overview
The 8444-1019 is a Woodward UMT 1 measuring transducer designed for three-phase electrical measurement in generator and power-distribution control systems. It measures true RMS voltage and current values and converts the calculated electrical parameters into configurable analog outputs for connection to higher-level control or monitoring equipment. This specific A6 configuration provides six analog outputs and a pulse output for kWh/kVARh energy measurement. Woodward documentation identifies the 8444-1019 as the 100 VAC, 5 A version of the UMT 1/A6 package, with a 24 VDC auxiliary supply. The unit includes a two-line LCD for displaying measured values and is suited to generator monitoring, load control, synchronization systems, and legacy power-generation installations.
Technical Specifications — 8444-1019
| Parameter | Value |
|---|---|
| Product Model | 8444-1019 |
| Manufacturer | Woodward |
| Product Type | UMT 1 Measuring Transducer |
| Configuration | UMT 1/A6 |
| Analog Outputs | 6 |
| Voltage Input | 100 VAC nominal |
| Current Input | 5 A AC |
| Measurement | True RMS, three-phase |
| Auxiliary Supply | 24 VDC |
| Frequency | 50/60 Hz |
| Analog Output Range | -20 to 20 mA, 0 to 20 mA, or 4 to 20 mA |
| Energy Pulse Output | kWh / kVARh |
| Display | 2-line, 16-character LCD |
| Housing | Type 1 |
| Mounting | Flush panel or DIN-rail/rear-panel, depending on configuration |
| Operating Temperature | -20°C to +70°C |
| Approx. Weight | 485 g |
Woodward’s official UMT 1 manual confirms true-RMS measurement, configurable analog outputs, LCD indication, and the available 1 A/5 A current-transformer and 100/400 VAC voltage-input configurations.

Woodward 8444-1019
Key Features and Benefits — 8444-1019
- Six configurable analog measurement outputs.
- 100 VAC voltage-transformer input.
- 5 A CT secondary input.
- True-RMS measurement for three-phase electrical systems.
- kWh and kVARh pulse-output capability.
- 24 VDC auxiliary power.
- Integrated LCD for local measurement display.
- Suitable for generator and power-distribution monitoring.
- Compatible with higher-level control systems through analog outputs.
The 5 A CT configuration is particularly important when selecting a replacement. Woodward also produced visually similar UMT 1 units for 1 A CT inputs and different voltage ranges, so matching only the UMT 1 family is not sufficient.
Related Models
8444-1002: UMT 1/A3 version with three analog outputs for 100 VAC and 5 A input.
8444-1057: UMT 1/A6 version configured for 400 VAC and 5 A input.
8444-1022: UMT 1/A3 version for 100 VAC and 1 A input with RS-485 Modbus communication.
LR21296: UMT 1/A6 version for 100 VAC and 1 A input.
Installation and Maintenance — 8444-1019
Before installation, verify the voltage-transformer ratio, 5 A CT secondary rating, auxiliary 24 VDC supply, analog-output configuration, and pulse-output wiring. Record existing scaling and parameter settings before removing the transducer.
During maintenance, inspect the CT and VT wiring, terminal connections, analog-output circuits, auxiliary power, and display operation. Never open-circuit an energized current-transformer secondary. After replacement, verify voltage, current, power, and energy readings against a calibrated reference.
Personally, I would confirm the 100 VAC / 5 A input configuration from the nameplate before approving a replacement. That detail distinguishes this unit from several closely related UMT 1 variants.
Product Warranty — 8444-1019
Warranty coverage should be confirmed according to the supplied condition, such as new surplus, refurbished, repaired, or tested-used. For critical generator-control spares, procurement records should include the complete part number, revision, input configuration, inspection status, serial number where available, and warranty period.
Woodward’s product-history service can be used to verify product information using the equipment label and part number.
When sourcing the Woodward 8444-1019, verify the UMT 1/A6 configuration, 100 VAC voltage input, 5 A current input, six analog outputs, and 24 VDC auxiliary supply before purchase.
中文版
Phone:
Email:
WhatsApp: