Description
Product Overview
The WOODWARD 5466-352 is a NetCon CPU-040 module used as a central processing component in legacy Woodward NetCon and MicroNet control systems. Woodward’s own product documentation identifies this part number as a NetCon CPU_040 module without LL memory, distinguishing it from the related CPU-040 version with LL memory.
The module performs core control-system processing and communication functions, making it an important component in installed turbine and engine control platforms. Available technical references identify a 68030 processor architecture, dual-ported RAM for VME-bus communication, and interfaces supporting network communication processors. For maintenance inventories, the main concern is configuration matching: CPU type, memory configuration, chassis generation, application software, and system architecture should all be checked before replacement.
Technical Specifications — 5466-352
| Parameter | Value |
|---|---|
| Product Model | 5466-352 |
| Manufacturer | Woodward |
| Product Type | NetCon CPU-040 Module |
| System Family | NetCon / MicroNet |
| CPU Architecture | 68030 microprocessor |
| Memory Configuration | Without LL Memory |
| Bus Interface | VME bus via dual-ported RAM |
| Network Processing | Supports network communication processors |
| Service Interface | Service panel communication on applicable systems |
| Mounting | NetCon / MicroNet chassis |
| Operating Temperature | Refer to the applicable system manual |
| Dimensions | Approx. 152 × 51 × 203 mm, depending on housing/configuration |
| Weight | Approx. 0.7–0.8 kg, supplier data varies |
| Status Indication | Front-panel LED indicators |
| Application | Industrial turbine and engine control |
Woodward’s parts listing specifically describes 5466-352 as “NetCon CPU_040, LL memory not included,” while the related 5466-351 is the LL-memory version.

WOODWARD 5466-352
Key Features and Benefits — 5466-352
- Central processing capability for legacy NetCon/MicroNet control platforms.
- 68030-based processing architecture.
- Dual-ported RAM provides the communication path to the VME bus.
- Supports communication with network processors within the control architecture.
- Service-panel access is available for applicable standalone MicroNet configurations.
- Watchdog logic can place the system into an IOLOCK state when a CPU failure is detected, de-energizing affected outputs and signals.
- Useful as an installed-base maintenance spare where the original CPU architecture must remain in service.
Related Models
5466-351: NetCon CPU-040 module with LL memory. It belongs to the same CPU family but has a different memory configuration, so it should not be assumed to be an interchangeable replacement.
5466-350: NetCon CPU-060 module, representing a different CPU configuration within the same legacy NetCon product family.
5466-353: NetCon main chassis transceiver used for chassis-level communication within the legacy control architecture.
5466-354: NetCon remote chassis transceiver designed for communication with remote chassis equipment.
Installation and Maintenance — 5466-352
Before replacing the module, document the existing CPU revision, chassis position, application configuration, memory configuration, and communication connections. Power isolation should follow the plant’s approved turbine-control maintenance procedure.
Inspect the card edge connector, PCB, mounting hardware, and front-panel indicators before installation. After replacement, verify CPU initialization, application loading, chassis communication, I/O status, and any active diagnostic indications.
Part-number matching alone is not sufficient for a legacy controller. The 5466-352 belongs to an older NetCon/MicroNet generation, and migration to newer Woodward platforms may require changes to the CPU, chassis, power supply, I/O hardware, and application software.
Product Warranty — 5466-352
Warranty coverage depends on the supplier, product condition, and purchase agreement. For a critical control-system spare, procurement records should include serial-number traceability, hardware revision, inspection or functional-test documentation, and clearly stated warranty terms.
The WOODWARD 5466-352 is best maintained as an exact-match legacy CPU spare when the installed NetCon/MicroNet architecture remains operational. Personally, I would verify the CPU memory configuration first; confusing the LL-memory and non-LL-memory variants is an easy mistake during emergency replacement.