Woodward 5466-1050 | MicroNet Simplex 48/24 High-Density Discrete I/O Module Woodward

The Woodward 5466-1050 is a MicroNet Simplex 48/24 High-Density Discrete I/O Smart-Plus module for Woodward MicroNet control systems.
Brand model:Woodward
Product Name: 5466-1050
Warranty: 1 year
Origin:USA
HS code:85389000.00
Inventory: Spot/Futures
Goods condition: Brand new
Delivery time: 3-4days/1month

Category: Brand:

Description

Product Overview

The Woodward 5466-1050 is a MicroNet Simplex 48/24 High-Density Discrete I/O Smart-Plus module for Woodward MicroNet control systems. Woodward identifies it as a simplex digital I/O module providing 48 discrete inputs and 24 discrete outputs. It is intended for turbine and other critical rotating-equipment control applications where a high concentration of discrete signals must be interfaced with the controller. The module is designed for installation in either full-size or narrow MicroNet chassis and uses compatible field termination modules. Woodward documentation also identifies software compatibility requirements for different coder revisions, so the installed application version should be checked during replacement planning.

Technical Specifications — 5466-1050

Parameter Value
Product Model 5466-1050
Manufacturer Woodward
Product Type MicroNet Simplex High-Density Discrete I/O Module
I/O Configuration 48 discrete inputs / 24 discrete outputs
Architecture Simplex
Product Family MicroNet / MicroNet Plus Smart-Plus
Input Type Discrete
Output Type Discrete
Chassis Compatibility Full-size or narrow MicroNet chassis
Field Termination Compatible 48/24 or related discrete FTM
Power System backplane supplied
Communication / Protocol MicroNet system backplane interface
Calibration No field calibration required
Mounting MicroNet chassis card slot
Dimensions (HxWxD) Approx. 222 × 80 × 266 mm, source-dependent
Weight Approx. 2.16 kg, supplier-reported
Storage Temperature -40 to +105°C
Pollution Degree 2
Woodward 5466-1050

Woodward 5466-1050

Woodward lists 5466-1050 as the MicroNet Simplex 48/24 HDDIO Smart-Plus module. Available technical references also identify it as a no-calibration module with either full-size or narrow chassis compatibility.

Key Features and Benefits — 5466-1050

  • 48 discrete inputs and 24 discrete outputs in one high-density module.
  • Simplex architecture for compatible MicroNet control systems.
  • Smart-Plus design intended for higher-density discrete signal handling.
  • Compatible with established MicroNet field termination arrangements.
  • No potentiometer adjustment or routine field calibration is required.
  • Suitable for turbine, compressor, and generator-control applications.
  • Supports lifecycle replacement where legacy MicroNet hardware remains in operation.
  • Woodward documentation identifies software/coder compatibility requirements, so system version should be verified before installation.

For spare-parts control, I would keep the module together with its applicable FTM and configuration records. The hardware is only one part of a successful I/O replacement.

Related Models

Woodward 5466-1051 — TMR version of the high-density 48-input/24-output Smart-Plus discrete I/O architecture.

Woodward 5466-1158 — Backward-compatible simplex 48/24 discrete I/O spare intended for selected legacy systems.

Woodward 5466-1105 — MicroNet speed/analog I/O combination module with four speed inputs, twelve selectable I/V inputs, and four 4–20 mA outputs.

Woodward 5466-5025 — High-density analog I/O module providing 24 selectable analog inputs and eight isolated 4–20 mA outputs.

Installation and Maintenance — 5466-1050

Before replacement, isolate the relevant MicroNet power supplies and follow Woodward’s approved maintenance procedure. Record the chassis slot, FTM connections, software/coder revision, and I/O configuration before removing the existing card.

Inspect the card-edge connector, field termination cables, chassis guides, and module indicators for contamination or physical damage. After installation, verify representative input and output channels individually before returning the turbine-control system to normal operation. Personally, I would confirm the coder/software compatibility first; Woodward specifically documents software-version restrictions for this module family.

Product Warranty — 5466-1050

Warranty coverage depends on supplier, condition, testing status, and purchase agreement. For used or refurbished inventory, request functional-test documentation covering representative digital input and output channels and confirm the hardware revision. The Woodward 5466-1050 should be matched to the MicroNet chassis, field termination arrangement, application software, and turbine-control configuration before commissioning.