Foxboro FBM217 P0914TR | 32-Channel Discrete Input Interface Module FOXBORO

$7,815.00

The FBM217 P0914TR is a 32-channel discrete input interface module for the Foxboro I/A Series distributed control system. It is designed to acquire discrete field signals and transfer their status through the redundant module Fieldbus to the associated Field Control Module or Field Control Processor.
Brand model:Foxboro
Product Name: FBM217 P0914TR
Warranty: 1 year
Origin:USA
HS code:85389000.00
Inventory: Spot/Futures
Goods condition: Brand new
Delivery time: 3-4days/1month

Category: Brand:

Description

Product Overview

The FBM217 P0914TR is a 32-channel discrete input interface module for the Foxboro I/A Series distributed control system. It is designed to acquire discrete field signals and transfer their status through the redundant module Fieldbus to the associated Field Control Module or Field Control Processor. The standard configuration provides 32 group-isolated DC voltage-monitoring inputs, with logic zero defined as 0–5 VDC and logic one as 15–30 VDC. With the appropriate termination assembly, the module can also interface with higher-voltage AC/DC discrete signals and contact inputs. Its compact design, configurable input filtering, diagnostic capabilities, and optional redundant installation make it suitable for process plants where dependable status monitoring is required.

Technical Specifications — FBM217 P0914TR

Parameter Value
Product Model FBM217
Part Number P0914TR
Manufacturer Foxboro / Schneider Electric
Product Type Discrete Input Interface Module
System Foxboro I/A Series DCS
Input Channels 32 group-isolated
Standard Input 15–30 VDC logic input
Logic Zero 0–5 VDC
Logic One 15–30 VDC
Typical Input Current 2.2 mA at 30 VDC
Filter / Debounce 0, 4, 8, 16, or 32 ms
Maximum Pulse Rate 250 Hz
Module Supply 24 VDC (+5%, -10%)
Power Consumption Approx. 3 W
Fieldbus Redundant 2 Mbps module Fieldbus
Mounting Modular baseplate / DIN rail or 19-inch rack
Weight Approx. 284 g
Operating Temperature -20°C to +70°C
Humidity 5–95% RH, non-condensing

The module itself provides the basic 32-channel interface, while the termination assembly determines the specific field signal arrangement. Supported TA configurations include 30 VDC logic/contact sensing and higher-voltage AC/DC inputs.

Key Features and Benefits — FBM217 P0914TR

  • 32 discrete input channels in a compact module.
  • Group isolation between field input groups.
  • Redundant 2 Mbps module Fieldbus communication.
  • Configurable input filtering for contact bounce and noise.
  • Supports pulse counting up to 250 Hz.
  • Can be installed in redundant pairs with the appropriate adapter.
  • Compatible with several termination assemblies for different field voltages.
  • LEDs provide operational and input-status indication.
  • Suitable for demanding process-control environments.

One important point: the termination assembly is part of the signal interface. The module should therefore be ordered and replaced together with the correct TA configuration when the field voltage or contact-sensing arrangement differs from the standard 15–30 VDC setup.

Related Models

FBM214: Foxboro I/A Series module designed for HART analog input applications.

FBM215: Related HART output interface module for process instrumentation.

FBM216: HART input interface module used for additional analog field-device integration.

FBM218: Related discrete output interface module within the I/A Series FBM family.

Installation and Maintenance — FBM217 P0914TR

Before replacement, record the existing termination assembly, field voltage, channel assignments, baseplate position, and redundancy configuration. Check the associated Fieldbus connections and verify that the replacement is compatible with the installed I/A Series architecture.

During maintenance, inspect the module connector, baseplate, termination assembly, field wiring, and Fieldbus cable. If an individual input appears faulty, verify the field switch, transmitter, wiring, and TA before replacing the FBM.

Personally, I would check the termination assembly first. The same module can be used with different field-signal arrangements, so replacing the card without confirming the TA can lead to an incorrect diagnosis.

Product Warranty — FBM217 P0914TR

Warranty coverage should be confirmed according to the supplied condition, such as new surplus, refurbished, or tested-used. For critical DCS spares, procurement records should include the complete part number, hardware revision where applicable, inspection status, serial information, and warranty period.

When sourcing the FOXBORO FBM217 P0914TR, verify the termination assembly, field voltage, baseplate configuration, and redundancy requirements before purchase. The published Foxboro documentation confirms P0914TR as the module part number and identifies the corresponding termination assemblies for its supported input configurations.

FOXBORO P0926GU FBM230 | FBM201 RH914SQ | FBM201 P0916AA
FOXBORO FBM232 P0926GW | FBM202 RH928CN | FBM203 RH914SV
FOXBORO FDC280 RH101FQ | FDC280 RH101FC | FDC280 RH101FF
FOXBORO H92 H92A049E0700 | FBM237 | P0973BM | AD202MU
FOXBORO FCP270 P0917YZ | FBM207B | RH916TA | RH924YA
FOXBORO H90 H90C9AA0117S | Compact programmable logic controller (PLC)