Description
- Model: CC-IP0101
- Part Number: 51410056-175
- Brand: Honeywell
- Series: Experion PKS / Series C
- Core Function: Connects PROFIBUS DP devices to Honeywell control systems
- Type: PROFIBUS DP Gateway / Fieldbus Interface Module
- Key Specs: Up to 12 Mbps PROFIBUS DP, up to 127 devices, 24 VDC supply
Product Introduction
The HONEYWELL CC-IP0101 51410056-175 is a PROFIBUS DP Gateway Module used with Honeywell Experion PKS and C300-based control architectures. Its main job is straightforward: provide a controlled interface between a PROFIBUS DP network and the Honeywell DCS, allowing field devices such as remote I/O and drives to exchange process data with the control system.
For an existing plant, the configuration details matter. Supplier technical listings specify support for up to 127 PROFIBUS devices and baud rates from 9.6 kbps to 12 Mbps, with a 24 VDC supply. Some secondary listings are inconsistent on environmental and electrical details, so those values should be confirmed against the installed revision and Honeywell documentation before procurement.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Model | CC-IP0101 |
| Part Number | 51410056-175 |
| Manufacturer | Honeywell |
| Product Type | PROFIBUS DP Gateway Module |
| System Family | Experion PKS / Series C |
| Controller Compatibility | Honeywell C300 architecture |
| Fieldbus | PROFIBUS DP |
| Maximum PROFIBUS Devices | Up to 127 devices |
| PROFIBUS Baud Rate | 9.6 kbps to 12 Mbps |
| Power Supply | 24 VDC ±10% |
| Typical Power Consumption | Approx. 7 W |
| Operating Temperature | 0°C to +60°C, supplier-listed |
| Storage Temperature | -40°C to +85°C, supplier-listed |
| Mounting | Honeywell Series C I/O architecture |
| Form Factor | Series 8 with IOTA and electronics module |
| Approx. Weight | 0.42 kg |
The listed communication and power specifications come from current secondary industrial catalogs. Honeywell-specific system documentation should take precedence when the exact hardware revision differs.

HONEYWELL CC-IP0101 51410056-175
Application and Selection Notes
The module is intended for installations where existing PROFIBUS DP field equipment needs to remain connected to a Honeywell Experion PKS control environment. Typical devices include distributed I/O, motor drives, process instrumentation, and other PROFIBUS DP slaves.
There is one important distinction: this is a gateway/interface module, not a standalone PLC CPU. Its usefulness depends on the C300 and Series C infrastructure around it. The module also appears in supplier catalogs as a discontinued Honeywell product, so actual physical stock should be confirmed rather than relying on catalogue availability.
For replacement work, match the complete part number. Do not substitute another Honeywell fieldbus module simply because its housing looks similar.
Advantages and Limitations
Advantages
- PROFIBUS DP connectivity for Honeywell control systems
- Supports up to 127 configured field devices according to supplier documentation
- Baud rates up to 12 Mbps
- Designed around Honeywell Series C/C300 architecture
- Useful for maintaining established PROFIBUS infrastructure
- Suitable as a dedicated MRO spare for legacy Experion installations
Limitations
This module is architecture-specific. It should not be treated as a universal PROFIBUS-to-Ethernet converter.
Public supplier information also contains conflicting descriptions of the module’s electrical interfaces. Therefore, unsupported claims about generic Ethernet ports, analog I/O channels, or alternative protocols should not be used for engineering approval. The exact cabinet configuration and Honeywell documentation should control.
Global Procurement and Shipping Notes
| Item | Recommended Handling |
|---|---|
| Condition | Confirm New Original, New Surplus, or Refurbished |
| Stock Status | Verify physical inventory before PO |
| Hardware Revision | Record actual revision from nameplate |
| Lead Time | Confirm actual warehouse availability |
| Warranty | State clearly on quotation and PI |
| Packaging | ESD bag + cushioning + rigid carton |
| Export Documents | Commercial Invoice, Packing List, COO when required |
| Shipping | Air courier for urgent MRO requirements |
| Incoterms | FCA, EXW, FOB, or DAP |
| Customs Description | Honeywell PROFIBUS DP gateway module |
| Country of Origin | Confirm from physical label and supplier documentation |
For international procurement, show both CC-IP0101 and 51410056-175 on the Commercial Invoice and Packing List. “PROFIBUS DP gateway module” is a clearer customs description than simply “electronic board.”
Quality Inspection and Test SOP
1. Inbound inspection
Verify the model, full part number, serial number, revision, IOTA/interface hardware, connectors, and housing condition. Check for corrosion, impact damage, contamination, or signs of previous repair.
2. Live test
Use a compatible Honeywell C300/Series C test environment. Verify power-up diagnostics, module recognition, PROFIBUS DP master communication, slave discovery/configuration, and representative cyclic data exchange. Record actual results in a Test Report.
3. Electrical testing
Check supply polarity, grounding continuity, and applicable electrical parameters. Do not apply an arbitrary 500 V megohmmeter test directly across sensitive electronic circuitry unless the manufacturer’s procedure explicitly permits it.
4. Configuration verification
Record accessible hardware and firmware revisions. Back up the PROFIBUS configuration and photograph the existing connections before removing an installed module.
5. Final QC
Place the module in an ESD bag, add shock protection, use a rigid carton, and attach a QC Passed label with the inspection date. Test photographs or video can be supplied when the stated test has actually been completed.
Common Replacement Risks
PROFIBUS configuration mismatch: Check slave addresses, baud rate, GSD files, device parameters, and cyclic data mapping before commissioning.
C300 compatibility: The gateway belongs to a specific Honeywell control architecture. Verify the controller, I/O link, carrier, and system revision before installation. Honeywell’s Series C documentation identifies the IOLINK as the interface used by C300 controllers to communicate with Series C I/O.
Part-number mismatch: Do not buy by CC-IP family name alone. The complete 51410056-175 suffix should be matched.
Network termination: PROFIBUS DP requires correct cable shielding and termination. A poor termination setting can produce intermittent communication faults that look like a gateway problem.
ESD: Use a grounded wrist strap and ESD-safe work surface. It is especially important when handling a replacement module outside its cabinet.
One field habit is still worth following: photograph the PROFIBUS connector and configuration before removing the old module. It makes restoration much less painful.
Related Models
CC-PDIL01 51405040-175: Honeywell Series C I/O interface hardware listed alongside the CC-IP0101, but it serves a different function and should not be considered a direct replacement.
CC-PDIH01 51405041-175: Related Honeywell Series C I/O hardware with a different function and part-number configuration.
CC-PDIL02 51405040-275: Related Series C I/O module variant; verify the complete configuration before substitution.
CC-PDOB01 51410070-175: Related Honeywell Series C module with a different I/O function.
Quick Conclusion
- Honeywell PROFIBUS DP Gateway Module.
- Part number: 51410056-175.
- Used with Honeywell Experion PKS / C300 control architecture.
- Supplier data specifies up to 127 PROFIBUS devices and baud rates up to 12 Mbps.
- 24 VDC supply is listed for the module.
- Best suited to maintaining an existing Honeywell PROFIBUS DP installation.
- ⚠️ Verify hardware revision, C300 compatibility, PROFIBUS configuration, and physical stock before purchase.
FAQ
What is the HONEYWELL CC-IP0101 51410056-175?
It is a Honeywell PROFIBUS DP Gateway Module used to connect PROFIBUS field devices with Honeywell control-system architecture.
How many PROFIBUS devices can it support?
Current supplier specifications list support for up to 127 devices, with baud rates from 9.6 kbps to 12 Mbps.
What power supply does it use?
Supplier technical data specifies 24 VDC ±10% and approximately 7 W power consumption. Verify the actual revision before installation.
Is it a PLC CPU?
No. It is a PROFIBUS DP gateway/fieldbus interface module designed to integrate field devices into the Honeywell control architecture.
Is it still manufactured?
At least one industrial supplier identifies the exact part as discontinued by the manufacturer, while other suppliers continue to advertise stock. Confirm actual physical inventory and lifecycle status before ordering.
What should buyers verify before purchase?
Confirm the complete part number, hardware revision, C300/Series C compatibility, PROFIBUS configuration, condition, test status, warranty, country of origin, and actual warehouse stock.
中文版
Phone:
Email:
WhatsApp: