Description
HIMA F8627 – Ethernet Communication Module for Safety Systems
Product Overview
The HIMA F8627 is a high-performance ethernet communication module specifically engineered for HIMA H41q and H51q safety systems. It enables seamless data exchange between central processing units and distributed modules, addressing the critical need for reliable communication in safety-critical industrial environments. This module supports both safety-related and non-safety-related data transfer, eliminating the need for separate networks and simplifying system architecture. Compliant with strict safety standards, it ensures stable operation in harsh industrial settings, making it suitable for oil, gas, chemical, and power generation sectors where uninterrupted communication is vital.
Technical Specifications — F8627
| Parameter | Value |
|---|---|
| Product Model | F8627 |
| Manufacturer | HIMA |
| Product Type | Ethernet Communication Module |
| Power | 24 VDC (±10%), typical 1A |
| Communication / Protocol | Safe Ethernet, OPC DA, Modbus TCP Slave, Elop II TCP |
| Operating Temperature | -20 °C to +60 °C |
| Mounting | Rack slot type (3 HU height, 4 SU width) |
| Dimensions (HxWxD) | 35 mm x 150 mm x 125 mm |
| Weight | 0.14 kg (net) |
| Typical Interfaces | 100Base-T RJ45, HSR RJ-12 |
| Compliance | CE, ROHS, IEC 61508 SIL 3 |

HIMA F8627
Key Features and Benefits — F8627
- Supports redundant communication configuration, ensuring uninterrupted operation even in case of single port failure.
- Integrates 100Base-T ethernet interface with RJ45 connector, enabling fast and secure data transfer between H41q/H51q systems.
- Compatible with HIMA OPC server for non-safety-related data exchange and Safe Ethernet for safety-critical data transmission.
- Equipped with 6 LED diagnostic indicators and 2 DIP switches for easy function setting and fault identification.
- Modular design allows hot-swap replacement, reducing system downtime during maintenance.
Related Models
- F8627X: Enhanced version of F8627, supporting additional protocols and compatible with OS version 4.x and higher.
- F8650X: Safe CPU module for H41q/H51q systems, seamlessly paired with F8627 for complete safety control.
- F7131: HIMA communication module, ideal for applications requiring Profibus DP slave protocol support.
- F3423: HIMA safety module, compatible with F8627 in complex industrial automation setups.
Installation and Maintenance — F8627
- Install the module in H41q/H51q system racks following HIMA’s installation guidelines, ensuring proper grounding and power supply.
- Configure communication parameters via DIP switches and HIMA engineering tools for optimized performance.
- Regularly check LED indicators to monitor module status and identify potential faults promptly.
- Perform hot-swap replacement only when the system is in a safe state to avoid operational disruptions.
- Ensure firmware is updated to the latest version to maintain compatibility and safety compliance.